OM-310 protects equipment against poor mains parameters. It can fully disconnect the load if power consumption exceeds the primary threshold for a user-defined period, or partially disconnect the load if the secondary threshold is exceeded. It measures and displays three-phase network parameters: actual phase and line voltages, positive-, negative- and zero-sequence voltages, phase currents, active, reactive and apparent load power, and power factor cos φ. It provides fault notification and remote load switching through an RS-232 / RS485 interface or an external switch. Built-in current transformers support loads from 2.5 kW to 30 kW. External current transformers allow loads up to 350 kW, including in networks with an isolated neutral. Protection covers unacceptable voltage surges, phase loss, incorrect phase sequence, phase coincidence, phase/line voltage imbalance, excessive current in any load phase and earth leakage. Automatic load reconnection can be enabled or disabled separately for each protection type. Electrical equipment is protected by controlling the coil of a magnetic starter or contactor.